6
Mating Connector
Vicor part # Amp part #
Housing 24795 2-794657-0
Contacts 24796 1-106529-2
Kit 24828
7
Parallel/Redundant Connections Parallel/Redundant Connections
L
O
A
D
PR bus leads should be connected
to like pin #s on redundant arrays
when equipped with optional
current share transformer.
*Removable jumpers in J4 are factory installed for local sensing. For remote
sensing the +Sense pins should be tied to the same point on the +Out power
bus; the -Sense pins should be tied to the same point the -Out power bus.
** There should be one master module, this is realized by choosing one
module to be the master and shorting the SC to S on the other module.
Units configured from the factory as paralled will already have this
configured.
Pin # Conn. Function Mating Conn.
1 Vout
J4-1 Vout
J4-2 – Sense
J4-3 Secondary Control P/N 16385
J4-4 + Sense
J4-5 + Vout
*Removable
Jumper
*Removable
Jumper
Factory Installed
Mini/Maxi LugMate
*
P
/N 16385
J4
1
5
1
5
1
5
*
P/N 16385
J4
1
5
#10-32 torque 16 in. lbs.
1
11
20
10
Input Connector
(View looking into J1)
*
P/N 16385
1
5
J4
Pin # Function
1-4 Vin
5-7 +Vin
8 NC /PR bus
9 PE protective earth
10 – Remote enable
11-13 Vin
14-17 +Vin
18 NC /PR bus
19 PE protective earth
20 + Remote enable
VA-J & VA-K configurations only
(300 & 375 Vin single Maxi &
single Mini)
Pin # Function
1-3 Vin
4-6 +Vin
7 NC
8 NC /PR bus
9 PE protective earth
10 – Remote enable
11-13 Vin
14-16 +Vin
17 NC
18 NC /PR bus
19 PE protective earth
20 + Remote enable
To disable output(s) apply +5 Vdc
between pins 10 and 20 in the polarity
indicated